10E-TECH ET8 (V4) CONTROL PANEL – INSTALLER MANUALKEYPADZone is sealedZone is unsealed, or Power faultor System is Armed,or phone line faultDisarmedDi
11E-TECH ET8 (V4) CONTROL PANEL – INSTALLER MANUALOPERATION SUMMARYARMDISARMMONITOR MODEPANICKEYPAD DURESSEXCLUDING ZONESALARM MEMORYor...or...or...or
12PROGRAMMINGE-TECH ET8 (V4) CONTROL PANEL – INSTALLER MANUALQUICK START PROGRAMMINGUse one of these programming summaries for fast setup of your ET8
13PROGRAMMINGE-TECH ET8 (V4) CONTROL PANEL – INSTALLER MANUAL[INSTALLER CODE]Factory default Installer Code: 000000[MASTER CODE]Factory default Master
14PROGRAMMINGE-TECH ET8 (V4) CONTROL PANEL – INSTALLER MANUALUSER CODESUser codes are the 3 to 6 digit codes used to operate the panel by keypad.User
15PROGRAMMINGE-TECH ET8 (V4) CONTROL PANEL – INSTALLER MANUALENTRY DELAY TIME1The Entry Delay Time 1 is the time given to Disarm the Panel after a Ent
16PROGRAMMINGE-TECH ET8 (V4) CONTROL PANEL – INSTALLER MANUALVIBRATION SENSITIVITYEach zone has individually adjustable sensitivity for connection of
17PROGRAMMINGE-TECH ET8 (V4) CONTROL PANEL – INSTALLER MANUALDOUBLE TRIGGER ZONESZones programmed to Double Trigger will recognise an alarm condition
18PROGRAMMINGE-TECH ET8 (V4) CONTROL PANEL – INSTALLER MANUALHANDOVER ZONESHandover zones are delayed only if entry is made through an Entry Delay zon
19PROGRAMMINGE-TECH ET8 (V4) CONTROL PANEL – INSTALLER MANUALDAY ZONESDay Zones operate when the panel is fully disarmed, i.e. when Area 1, Area 2and
HEAD OFFICE:E-Tech Security Products Pty LtdABN 000 110 11012 Security CloseSafe Hills NSW 2147 AustraliaPh +61 23 9988 7766Fax +61 23 9988 7765“Austr
20PROGRAMMINGE-TECH ET8 (V4) CONTROL PANEL – INSTALLER MANUALDEFINITIONArea Partitioning allows the 8 zones to be split into twopartitions; Area1 and
21PROGRAMMINGE-TECH ET8 (V4) CONTROL PANEL – INSTALLER MANUALP47E, P48EDESCRIPTION:Area 1 User CodesPROGRAM MODE LEVEL:Installer, Remote by PCFACTORY
22PROGRAMMINGE-TECH ET8 (V4) CONTROL PANEL – INSTALLER MANUALZONE TO OUTPUT MAPPINGWhen a zone alarms, it can turn on any or all of the following 6 ou
23PROGRAMMINGE-TECH ET8 (V4) CONTROL PANEL – INSTALLER MANUALP57EPROGRAM MODE LEVEL:Installer, Remote by PCFACTORY DEFAULT:all ON: All zones trigger S
24PROGRAMMINGE-TECH ET8 (V4) CONTROL PANEL – INSTALLER MANUALENTRY BEEPSThe sonalert will beep during Entry Delay.PROGRAMMING SEQUENCE:P60E 1E toggles
25PROGRAMMINGE-TECH ET8 (V4) CONTROL PANEL – INSTALLER MANUALTAMPER ALARM LOCKOUTThis option programs the Tamper input to Lockout, i.e. cause the Sire
26PROGRAMMINGE-TECH ET8 (V4) CONTROL PANEL – INSTALLER MANUALTAMPER ALARM / OUTPUT MAPPINGThis option selects which outputs will trigger when a Tamper
27PROGRAMMINGE-TECH ET8 (V4) CONTROL PANEL – INSTALLER MANUALSYSTEM OPERATION SHORTCUTSSome keypad operations can be programmed to operate with or wit
28PROGRAMMINGE-TECH ET8 (V4) CONTROL PANEL – INSTALLER MANUALMONITOR MODE OUTPUT MAPPINGThis option selects which outputs are triggered by alarms in M
29PROGRAMMINGE-TECH ET8 (V4) CONTROL PANEL – INSTALLER MANUAL2 SECOND MONITOR MODE ALARMAlarms in Monitor Mode can either activate the programmed outp
CONTENTSIntroduction ... 4Features ...
30PROGRAMMINGE-TECH ET8 (V4) CONTROL PANEL – INSTALLER MANUAL50Hz MAINS FREQUENCYSelects either 50Hz or 60Hz mains power frequency operation. Leave th
31PROGRAMMINGE-TECH ET8 (V4) CONTROL PANEL – INSTALLER MANUALSUPERVISED RADIO ZONESThis option assigns zones that will operate as Radio Supervised typ
32PROGRAMMINGE-TECH ET8 (V4) CONTROL PANEL – INSTALLER MANUALRADIO SUPERVISION ALERTS – RESET OUTPUTSetting this option turns the Reset output ON when
33PROGRAMMINGE-TECH ET8 (V4) CONTROL PANEL – INSTALLER MANUALRADIO SUPERVISION ALERTS – SIREN OUTPUTSetting this option turns the Siren output ON when
34PROGRAMMINGE-TECH ET8 (V4) CONTROL PANEL – INSTALLER MANUAL3K3 ZONE RESISTORSSetting this option ON changes the Zone 1 to Zone 8 (and External Tampe
35PROGRAMMINGE-TECH ET8 (V4) CONTROL PANEL – INSTALLER MANUAL24HR ZONE FIRE SIREN SOUNDThis option changes the siren sound when a 24hr zone is trigger
36PROGRAMMINGE-TECH ET8 (V4) CONTROL PANEL – INSTALLER MANUALARM1 PULSE OUTPUTThis option selects the ARM1 output to pulse on for 2 seconds wheneverar
37PROGRAMMINGE-TECH ET8 (V4) CONTROL PANEL – INSTALLER MANUAL6 BEEPS ON ARMINGNormally the keypad/s onboard SONALERT gives 3 beeps when the ET8 isArme
38PROGRAMMINGE-TECH ET8 (V4) CONTROL PANEL – INSTALLER MANUALTELEPHONE NUMBERS 1 & 2The ET8 can dial up to 2 phone numbers when an event is to be
39PROGRAMMINGE-TECH ET8 (V4) CONTROL PANEL – INSTALLER MANUALTELEPHONE NUMBER 3 – TEST CALLSPhone Number 3 is used to send Test Calls. If it is not pr
4E-TECH ET8 (V4) CONTROL PANEL – INSTALLER MANUALThe E-TECH ET8 is a wholly Australian Designed and Manufactured productfrom E-Tech Security Products,
40PROGRAMMINGE-TECH ET8 (V4) CONTROL PANEL – INSTALLER MANUALREPORT ZONE ALARMSThis option selects which zone inputs will send Alarm reports to the Ce
41PROGRAMMINGE-TECH ET8 (V4) CONTROL PANEL – INSTALLER MANUALREPORT MISCELLANEOUS ALARMSREPORT MISCELLANEOUS RESTORALSThese options select which Misce
42PROGRAMMINGE-TECH ET8 (V4) CONTROL PANEL – INSTALLER MANUALTEST CALL INTERVALTest calls to the Central Station can be sent at intervals between 2 an
43PROGRAMMINGE-TECH ET8 (V4) CONTROL PANEL – INSTALLER MANUAL1E 2E 3E 4E 5E 6E 7E 8EON = Factory default setting.Disable diallerContact ID formatAudib
44PROGRAMMINGE-TECH ET8 (V4) CONTROL PANEL – INSTALLER MANUALCONTACT ID + AUDIBLE DTMF FORMATFor simultaneous Central Station and Audible Monitoring.T
45PROGRAMMINGE-TECH ET8 (V4) CONTROL PANEL – INSTALLER MANUAL1E 2E 3E 4E 5E 6E 7E 8EON = Factory default setting.Split dial Phone Nos.Check for dial t
46PROGRAMMINGE-TECH ET8 (V4) CONTROL PANEL – INSTALLER MANUAL1E 2E 3E 4E 5E 6E 7E 8EON = Factory default setting.AREA1 Open/Close reportAREA2 Open/Clo
47PROGRAMMINGE-TECH ET8 (V4) CONTROL PANEL – INSTALLER MANUALFORCED OPENING REPORTIf Forced Opening Report is selected ON – when an alarm has been res
48PROGRAMMINGE-TECH ET8 (V4) CONTROL PANEL – INSTALLER MANUAL1E 2E 3E 4E 5E 6E 7E 8EON = Factory default setting.Enable Test CallsMains Report delayLi
49PROGRAMMINGE-TECH ET8 (V4) CONTROL PANEL – INSTALLER MANUALSWINGER SHUTDOWNLimits the number of calls made by a zone alarm when Multiple Zone Alarms
5E-TECH ET8 (V4) CONTROL PANEL – INSTALLER MANUALINSTALLATION PROCEDURESThe location of the main panel housing should be in an area that is within the
50PROGRAMMINGE-TECH ET8 (V4) CONTROL PANEL – INSTALLER MANUAL1E 2E 3E 4E 5E 6E 7E 8EON = Factory default setting.Upload/DownloadDirect ConnectRemote A
51PROGRAMMINGE-TECH ET8 (V4) CONTROL PANEL – INSTALLER MANUALCALLBACK MODEEnables two methods of connecting by computer for remote upload/download.NO
52PROGRAMMINGE-TECH ET8 (V4) CONTROL PANEL – INSTALLER MANUALREQUIRED RINGSSets the number of double-rings before an incoming call is answered. This i
53PROGRAMMINGE-TECH ET8 (V4) CONTROL PANEL – INSTALLER MANUALCLEAR MEMORYEnter P96E when in Installer Program mode to clear all events in the Alarm me
54E-TECH RADIOE-TECH ET8 (V4) CONTROL PANEL – INSTALLER MANUALRADIO QUICK STARTPROGRAMMING RADIO KEYS:Select which User Codes 2–8 will be Radio Codes
55E-TECH RADIOE-TECH ET8 (V4) CONTROL PANEL – INSTALLER MANUALRADIO DEVICES – OPERATIONALARM: Any E-Tech Radio Device can operate on any zone 1–8 as p
56E-TECH RADIOE-TECH ET8 (V4) CONTROL PANEL – INSTALLER MANUALRADIO DEVICE PROGRAMMINGEach of the 8 zones of the ET8 can be a radio zone. Once program
57E-TECH RADIOE-TECH ET8 (V4) CONTROL PANEL – INSTALLER MANUALRADIO CODESEach of the 15 User Codes, except for the Master Code, can be programmed tobe
58E-TECH ET8 (V4) CONTROL PANEL – INSTALLER MANUALAUDIBLE MONITORINGWhile Central Station Monitoring is recommended, the ET8 can also sendaudible alar
59E-TECH ET8 (V4) CONTROL PANEL – INSTALLER MANUALOPERATING THE ET8 BY TELEPHONEThe ET8 will allow a user to call in tothe panel, using a standard DTM
6E-TECH ET8 (V4) CONTROL PANEL – INSTALLER MANUALCONNECTION DIAGRAMJ1J2RECEIVERPROGTAMPBATTERYE-TECH SECURITY PRODUCTS105-220TELEPHONEHEATSINKJ3AUX1AU
60E-TECH ET8 (V4) CONTROL PANEL – INSTALLER MANUALSWITCHESA variety of switches are available for protecting doors and windows.The line-up includes su
61E-TECH ET8 (V4) CONTROL PANEL – INSTALLER MANUALWIRELESS PRODUCTSRADIO ACCESSORIESAsk your installer about the range of E-Tech radio devices for th
62E-TECH ET8 (V4) CONTROL PANEL – INSTALLER MANUALP88EP89EP96EP97EP98EP91EP95EP90EP87EP85EP86EP83EP84EOPTION DESCRIPTION DEFAULT PAGE OPTION DESCRIPTI
63E-TECH ET8 (V4) CONTROL PANEL – INSTALLER MANUALDate purchased:INSTALLATION RECORDDate installed:Installation Company:Telephone:Monitoring Company:T
7E-TECH ET8 (V4) CONTROL PANEL – INSTALLER MANUALE-Tech ET8CONTROLPANELE-Tech ET8CONTROLPANELE-Tech ET8CONTROLPANELE-Tech ET8CONTROLPANEL0VALARMTAMPER
8E-TECH ET8 (V4) CONTROL PANEL – INSTALLER MANUALMONITORED ZONESThe E-Tech ET8 has 10 separate monitored inputs.• 8 x Fully programmable Zone inputs•
9E-TECH ET8 (V4) CONTROL PANEL – INSTALLER MANUAL12 VOLT OUTPUT:A regulated 13.8 VDC output is available to power detectors and otherequipment. This o