PROGRAMMING
E-TECH ET8 (V4) CONTROL PANEL INSTALLER MANUAL
SUPERVISED RADIO ZONES
This option assigns zones that will operate as Radio Supervised types.
Supervised signals failure is reported (as per the P66E output options) when no
signal is received from a Radio Supervision Zone for the Supervision Time
P67E.
Radio Supervision for any zone is not enabled unless a Radio PIR is assigned
to the zone, (P01EP08E).
PROGRAMMING SEQUENCE:
P65E [Zone No]E toggles the options ON and OFF
P65E [Zone No]E OFF: The zone is not a Supervised Radio zone
P65E [Zone No]E ON: The zone is a Supervised Radio zone
P65E
PROGRAM MODE LEVEL:
Installer, Remote by PC
FACTORY DEFAULT:
all OFF: No Radio Supervision zones
NOTES:
0E will turn all selections OFF
MEMORY E will turn all selections ON
RELATED OPTIONS:
P66E 1E6E Radio Supervision Alerts
P67E Radio Supervision Time
P01EP08E Programming Radio Devices
OPTION No DESCRIPTION 1 2 3 4 5 6 7 8
Zones
ON = Factory default setting
P65E Supervised zonesRadio
SUPERVISION TIME
The SUPERVISION TIME is the time allowed between radio transmissions
received by the ET8 from any Supervised E-Tech Radio PIR (100663).
The SUPERVISION TIME setting is from 01 to 24 hours.
PROGRAMMING SEQUENCE:
P67E existing time is displayed [ENTER NEW TIME] E new time is displayed
EXAMPLE: To program SUPERVISION TIME to be 4 hours:
P67E 04E
P67E
PROGRAM MODE LEVEL:
Installer, Remote by PC
FACTORY DEFAULT:
24hrs
NOTES:
A setting of less than 3 hours is not
recommended.
The Supervision timer is reset on exit
from Installer Program Mode, on Arm or
Disarm and on reception of the
Supervision signal from the particular
Radio PIR.
The Supervision signal from each
Supervised Radio PIR is individually
timed.
RELATED OPTIONS:
P65E Radio Supervision Zones
P66E 1E6E Radio Supervision Alerts
P66E 7E8E Supervision Time Speed-up
RADIO SUPERVISION
The purpose of Radio Supervision is to verify the correct operation of
E-Tech Radio PIRs. The Supervision signal from the Radio PIR tells the
panel that the device has not been removed from radio range and is
in working order.
Non-SUPERVISION Radio PIRs can also be programmed and used
with the ET8 SUPERVISION TIMERS.
A non-SUPERVISION enabled Radio PIR will transmit signals to the
ET8 only when it has detected an event. Obviously, there is no
guaranteed signal period.
In either case, when the allowed time limit is exceeded then a
WARNING is first given (if programmed by P66E 3E), and then after 1
minute, the programmed RADIO SUPERVISION ALERTS are
generated by the ET8.
NOTE: Manually Excluding a Supervised Zone will also disable Radio
Supervision for that zone.
RADIO SUPERVISION ALERTS, SUPERVISION TIME SPEEDUP
See pages 3233
P66E 1E6E
See Page 56 for
Radio Device programming